Enersys DX
The DataSafe™ DX range of flooded lead calcium flat plate batteries has been designed for
use in UPS applications, more specifically large data centers, which demand the highest levels of security and reliability. The proven reliability of DataSafe DX as a leading high rate
performance battery is backed by 20 + years of experience in the marketplace.
The DataSafe DX is an economical multi-cell calcium flat plate battery. Multi-cell construction requires fewer units, resulting in lower installation costs. While optimizing the
space available in the battery room, it delivers superior performance making the DataSafe DX a superlative cost-effective battery. The DataSafe DX features EnerSys’ time tested Slide-Lock™ post seal design, bolted lead plated copper connectors, optimal grid design, heavy duty plate lug and strap and dual lug design, which make this battery ideal for high rate applications.
All battery systems are rated at 100% capacity at initial discharge. The DataSafe DX has a 20 year life expectancy in float service at 77°F (25°C) ambient temperature.
Features
• Capacity range: 0.612 – 5.245 kW per cell
• Suitable for UPS & Switchgear applications
• Multi-cell construction
• Cover made from flame retardant PVC
• Container made from styrene acrylonitrile (SAN),
also flame retardant polycarbonate (PC) optional
• Long life Slide-Lock™ post seal design Standards
• Manufactured in EnerSys production facilities certified to ISO 9001: 2000
• Manufactured in EnerSys production facilities certified to ISO 14000: 1996
• Available testing to IEEE 450 standards as well as customer specific applications.
Specifications
Plate thickness:
Positive: 0.200 in/5.1 mm
Negative: 0.130 in/3.6 mm
Plate suspension type:
Positive: Bridge hung
Negative: Bottom supported
Container:
Styrene Acrylonitrile (SAN) Optional flame retardant polycarbonate (PC)
• Cover: Made from flame retardant PVC, UL94-VO/L.O.I. 28%
• Separators: Microporous plastic
• Bolt connectors: Stainless steel, English measure, Hex-Head
• Interunit connectors: Lead-plated copper
• Electrolyte over plates: 2.88 in/73.1 mm
• Vent type: Flame Arrestor, Fused Alumina
• Float voltage settings: Acceptable min/max: 2.17/2.26 Vpc, Recommended: 2.25 Vpc
• Sediment space: 1.04 in/26.4 mm
Posts:
Lead-plated copper
DX-5 to DX-25 – one positive post and one negative post per cell.
DX-27 to DX-35 – two positive posts and two negative posts per cell.
• Post seal type: Slide-Lock™
• Specific gravity: 1.215 standard (1.250 available upon request)